Fire protection empty enclosures
F30 hifire 4400
Empty fire protection enclosure for the
hifire 4400 fire alarm control panel with
a fire resistance period of
at least 30 minutes for
external and internal fire loads in
accordance with F30 and I30 (tested in accordance
with DIN 4102, DIN EN 1634-3, EN 13501-1,
EN 13501-2).
The fire protection enclosure is suitable for
the functional maintenance of distributors for
at least 30 minutes in the event of an
external fire load in the sense of E30
(tested in accordance with DIN 4102-12).
Based on the general
technical approval Z-86.1-5 in
the sense of I30 and Z-86.1-10 in the sense of E30
and F30 in accordance with MLAR 2005.
The functional verification of installations of the
hifire 4400 fire alarm control panel has been proven in
a fire test by a PÜZ body
certified in area
86.2.
Reviews